ICS Advisory

Omron CX-One

Last Revised
Alert Code
ICSA-18-100-02

1. EXECUTIVE SUMMARY

  • CVSS v3 5.3
  • ATTENTION: Low skill level to exploit.
  • Vendor: Omron
  • Equipment: CX-One
  • Vulnerabilities: Stack-based Buffer Overflow, Heap-based Buffer Overflow, Type Confusion.

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow remote code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of CX-One are affected:

  • CX-One Versions 4.42 and prior, including the following applications:
  • CX-FLnet versions 1.00 and prior,
  • CX-Protocol versions 1.992 and prior,
  • CX-Programmer versions 9.65 and prior,
  • CX-Server versions 5.0.22 and prior,
  • Network Configurator versions 3.63 and prior, and
  • Switch Box Utility versions 1.68 and prior.

3.2 VULNERABILITY OVERVIEW

3.2.1 HEAP-BASED BUFFER OVERFLOW CWE-122

Parsing malformed project files may cause a heap-based buffer overflow.

CVE-2018-8834 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:L).

3.2.2 STACK-BASED BUFFER OVERFLOW CWE-121

Parsing malformed project files may cause a stack-based buffer overflow.

CVE-2018-7514 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:L).

3.2.3 ACCESS OF RESOURCE USING INCOMPATIBLE TYPE (TYPE CONFUSION) CWE-843

Parsing malformed project files may allow the pointer to call an incorrect object resulting in an access of resource using incompatible type condition.

CVE-2018-7530 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:L).

3.3 BACKGROUND

  • Critical Infrastructure Sectors: Critical Manufacturing
  • Countries/Areas Deployed: Worldwide
  • Company Headquarters Location: Japan

3.4 RESEARCHER

Rgod, working with Trend Micro’s Zero Day Initiative, reported these vulnerabilities to NCCIC.

4. MITIGATIONS

Omron has released an updated version of CX-One to address the reported vulnerabilities. These releases are available through the CX-One auto-update service.

  • CX-FLnet version 1.10,
  • CX-Protocol version 1.993,
  • CX-Programmer versions 9.66,
  • Common Module including CX-Server version 5.0.23,
  • Network Configurator version 3.64, and
  • Switch Box Utility version 1.69

NCCIC recommends that users take the following measures to protect themselves from social engineering attacks:

NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT website.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities. These vulnerabilities are not exploitable remotely.

This product is provided subject to this Notification and this Privacy & Use policy.

Vendor

Omron